100 kW plant, 0.70 to 0.95
- Real power
- 100
- Present power factor
- 0.7
- Target power factor
- 0.95
- System
- Three-phase
- Voltage (line-to-line for three-phase)
- 400
- Frequency
- 50 Hz
Result Capacitor bank needed (kvar): 69.2
Capacitance (µF, per phase in delta): 458.6
Apparent power before (kVA): 142.9
Apparent power after (kVA): 105.3
Line current before (A): 206.2
Line current after (A): 151.9
Current reduction: 26.3%
- φ1 = arccos(0.7) → tan φ1 = 1.0202
- φ2 = arccos(0.95) → tan φ2 = 0.3287
- Qc = 100 kW × (1.0202 − 0.3287) = 69.15 kvar
- C per phase (delta) = Qc ÷ (3 × 2π × 50 × 400²) = 458.6 µF
- Current falls from 206.2 A to 151.9 A
A motor-heavy 400 V load at 0.70 lagging needs about 69 kvar of capacitors; apparent power drops from 142.9 kVA to 105.3 kVA.