3 kW drawn as 5 kVA
- Known values
- kW and kVA
- Real power (P)
- 3
- Apparent power (S)
- 5
Result Power factor: 0.600
Power factor as a percentage: 60%
Rating: Poor (below 0.80)
Phase angle φ (degrees): 53.13
Reactive power Q (kVAR): 4
Apparent power S (kVA): 5
- PF = P ÷ S = 3 kW ÷ 5 kVA = 0.6
- Q = √(S² − P²) = 4 kVAR
- φ = arccos(0.6) = 53.13°
A motor load reading 3 kW on the wattmeter but 5 kVA of apparent power runs at a power factor of 0.6, with 4 kVAR circulating as reactive power.